Detection Technology
How to Choose GIS Testing Equipment
At the handover test site of the substation, the testing work of GIS equipment often faces a practical problem: insufficient test voltage, difficulty in equipment handling, interference and distortion of partial discharge data... The root cause of these problems mostly points to the same link - improper selection of testing equipment. As the core equipment of substations, the insulation performance of GIS composite electrical appliances is directly related to the safe operation of the power grid. Choosing the right testing equipment is a prerequisite for ensuring accurate test data and efficient on-site operations.
Voltage and Capacity: The First Threshold for Selection
The selection of GIS testing equipment first needs to solve the problem of voltage level and capacity matching. GIS with different voltage levels have significant differences in their test voltage requirements. Taking 110kV GIS as an example, the AC withstand voltage test voltage usually needs to reach around 265kV, while the test voltage for 220kV level equipment is even higher. If the voltage output capability of the equipment is insufficient, the experiment cannot be carried out at all; On the contrary, if the capacity is selected too small, the power overload protection will frequently operate during the boosting process, and the test cannot be completed.
The UHV series variable frequency series resonant withstand voltage test device of Wuhan UHV Power Technology Co., Ltd. adopts the method of adjusting the power supply frequency to achieve resonance between the reactor and the tested capacitor, and can obtain high voltage and high current output at low input power. Taking the UHV-810kVA/270kV model as an example, this device can cover the AC withstand voltage test of 110kV switches and GIS, with a test frequency of 30-300Hz, while also meeting the withstand voltage requirements of various equipment such as 110kV cables and main transformers. The design concept of "one device covering multiple types of samples" has practical cost and time value for power supply companies and testing institutions that need to cope with diverse testing tasks.
In terms of capacity calculation, the core formula is not complicated: the required capacity for AC withstand voltage is P=ω CU ², where C is the capacitance of the test sample and U is the test voltage. However, the capacitance of GIS equipment is affected by factors such as bus length and chamber structure, and needs to be accurately estimated based on data provided by the manufacturer or on-site measurements. When selecting, it is recommended to leave a margin of 1.2 to 1.5 times the calculated value to ensure waveform quality and equipment operation stability.
Partial discharge measurement: the "delicate activity" of GIS detection
The withstand voltage test solves the problem of "whether it can withstand", while partial discharge measurement answers "whether there are hidden dangers inside". During the manufacturing, transportation, and on-site installation of GIS equipment, conductive impurities or assembly defects may be introduced. These minor issues may not be exposed during the withstand voltage test, but will gradually develop into insulation faults during long-term operation.
When selecting partial discharge measurement equipment, testing bandwidth and detection sensitivity are two key indicators. The ultra-high frequency electromagnetic pulse excited by internal discharge in GIS requires equipment with a sufficiently wide frequency band to effectively capture it. The UHVIW series GIS non partial discharge fault simulation test device for Wuhan UHV covers a testing bandwidth of 30kHz to 2.0GHz, and can provide various discharge spectra such as time-domain waveform, PRPD, PRPS, etc. It adopts non-invasive detection method and does not require power outage during the testing process. The high-voltage part of the device is completely enclosed in a closed space, and the overall partial discharge is controlled within 3pC. It can be used for experimental research, instrument assessment, and scientific research and teaching scenarios in GIS partial discharge detection.
For GIS equipment that has already been put into operation and is difficult to power off, UHF ultra-high frequency detection method is the preferred solution, supplemented by ultrasonic detection for auxiliary positioning. The UHV-2000C partial discharge detection system of Wuhan UHV integrates partial discharge measurement, positioning, and online monitoring functions. Filtering, data acquisition, graphic display, and test report generation can all be automatically completed, making it suitable for on-site operation and maintenance personnel to quickly get started.
Mechanical characteristics of switches: the "other half" that cannot be ignored
The testing of GIS equipment not only involves insulation performance, but also the mechanical characteristics of switches are equally critical. The opening and closing time, contact stroke, closing resistance and other parameters of the circuit breaker directly affect the operational reliability of the equipment in the event of a fault. When choosing a switch characteristic tester, anti-interference ability is the primary consideration - the electromagnetic environment at the substation site is complex, especially at 800kV level substations, where ordinary instruments are prone to data jumps due to interference.
The UHV-406 high-voltage switch dynamic characteristic tester (double terminal grounding) of Wuhan Ultra High Voltage is designed with anti-interference circuit, which can be reliably used in 800kV substations. It can also measure 12 metal contact fracture, 6 closing resistance, and 3 graphite contact tests, and is suitable for all models of SF6 switches, GIS combination devices, vacuum switches, and oil switches at home and abroad. The double ended grounding function solves the tedious operation of removing the grounding wire in traditional testing, and has significantly improved the efficiency of on-site operations.
Equipment form and portability: practical considerations for on-site operations
GIS testing is often conducted on-site at substations, and the convenience of equipment handling and wiring directly affects work efficiency. Traditional power frequency test transformers have a large volume and heavy weight, and a testing team often requires vehicles and multiple people to collaborate in order to complete equipment transportation. The variable frequency series resonant device requires only 1/Q of the test capacity, significantly reducing the overall weight and volume of the equipment. It can be driven by a 220V/380V single or three-phase power supply, making it more suitable for on-site mobile testing.
For detection tasks that require frequent transitions, vehicle mounted testing systems are another direction worth considering. The vehicle mounted high-pressure inflatable non partial discharge combination experimental device of Wuhan UHV adopts a vehicle mounted hydraulic lifting structure, and the high-pressure part is fully sealed in a shielded space, which ensures the safety and reliability of the test while being easy to move.
Behind the selection: Qualification and service are equally important
The hardware parameters of the device are certainly important, but the technical support capability and after-sales response speed of the supplier cannot be ignored. The on-site situation of GIS testing is complex, and equipment debugging to data analysis, it often requires timely cooperation the manufacturer's technical personnel.
In addition, whether the supplier has ISO9001 quality management system certification and possesses multiple patents and software copyrights are also reference indicators for measuring their technical strength. Wuhan UHV has been deeply involved in the field of high-voltage electrical testing for nearly 22 years, with product lines covering multiple directions such as series resonance, partial discharge testing, transformer testing, circuit breaker testing, etc. Its equipment has been applied and verified in multiple projects at home and abroad.
Choosing GIS testing equipment is essentially finding a balance between technical parameters, on-site adaptability, service support, and cost. There is no one size fits all solution, only by comprehensively judging based on the voltage level, capacitance, test standards, and on-site conditions of the specific tested equipment, can the truly suitable testing equipment be selected.