Choose Cable Testing Equipment for XLPE Cables

time:2026/10/10   source:Wuhan UHV  reading:437 time

In the power system, cross-linked polyethylene (XLPE) insulated cables have dominated the field of medium and high voltage transmission due to their excellent electrical performance and mechanical strength. With the acceleration of urban power grid renovation and new energy grid integration projects, the demand for XLPE cable handover tests and preventive tests continues to rise. However, facing the wide variety of testing equipment in the market, how to scientifically select has become a practical problem faced by many power workers. Wuhan UHV Power Technology Co., Ltd. has developed a systematic selection approach through long-term technical service practice.


Series Resonant System


The first step is to clarify the selection logic of equipment types

XLPE cable insulation is extremely sensitive to space charges, and DC withstand voltage tests can accumulate space charges in the insulation layer, causing insulation damage or even breakdown. Therefore, for the withstand voltage test of XLPE cables, the industry consensus is that it is strictly prohibited to prioritize the use of DC withstand voltage equipment, and AC withstand voltage equipment should be selected instead. The current mainstream AC withstand voltage solutions include very-low frequency (0.1Hz) withstand voltage and variable frequency series resonant withstand voltage, each suitable for different cable voltage levels and site conditions.


Voltage level and capacity matching are core parameters

The first principle of selection is that the rated voltage of the equipment must cover the test voltage requirements of the tested cable. According to industry experience, the corresponding test voltage for 10kV cables is about 22kV, and it is recommended to choose models of 30kV or higher; The test voltage for a 35kV cable is approximately 52kV, and it is recommended to use models of 80kV or higher. The UHV-500kVA/200kV variable frequency series resonant withstand voltage test device for Wuhan UHV can meet the AC withstand voltage test requirements 6km of 10kV/300mm ² cable to 0.6km of 110kV/300mm ² cable. The system operates within a frequency range of 30-300Hz, with an output waveform of sine wave and waveform distortion rate controlled at a low level.

Capacity selection cannot be ignored either. The capacitance of a cable is directly related to its length and cross-sectional area. For example, a 25kV XLPE cable has a capacitance of approximately 0.2 to 0.4 μ F per kilometer. The maximum load capacitance of the equipment at 0.1Hz determines the length of the cable that can be tested in a single test. Wuhan UHV recommends that users reserve a 20% capacity margin when selecting to avoid instability during the boosting process.


The accuracy index determines the credibility of the experimental results

The measurement accuracy of testing equipment directly affects the judgment of cable insulation status. For very-low frequency high-voltage generators, the voltage accuracy should be ≤ 3%, and it must be declared that the data is directly sampled the high-voltage side to avoid the "capacity rise effect" error caused by low-voltage conversion; The waveform distortion should be ≤ 5%, as waveform distortion can seriously affect the equivalence of test results. The new generation intelligent very-low frequency high voltage generator of Wuhan UHV supports multiple frequency outputs of 0.1Hz, 0.05Hz, 0.02Hz, and 0.01Hz. The addition of the 0.01Hz gear on the basis of 0.05Hz and 0.02Hz significantly improves the equipment's load capacity.


Different types of devices are suitable for different scenarios

For the handover and preventive testing of long-distance, large section XLPE cables, the frequency conversion series resonant deviceis the preferred solution. Its advantage is that it can obtain a larger test capacity with a smaller power capacity, and the equipment is lightweight and easy to move on site. For daily inspection and preventive testing of cables of 35kV and below, very-low frequency high voltage generators have the advantage of portability, which can effectively detect insulation defects such as water and tree branches in cables. The series of cable fault testers for Wuhan UHV includes models such as UHV-501 fully intelligent multiple pulse cable fault tester, which integrates fault distance measurement function and supports multiple testing modes such as low-voltage pulse method, high-voltage flashover method, and intelligent multiple pulse method. It can cope with different types of cable problems such as low resistance short circuit, high resistance leakage, and flashover faults.


Choosing the right equipment is the first step towards successful cable testing. Wuhan UHV Power Technology Co., Ltd. provides a full process service equipment selection to technical support for users in the power industry with a multi-dimensional product system covering fault location, AC withstand voltage, and partial discharge detection.