| Time measurement |
12 natural switching (closing) time |
| The opening (closing) phase is not at the same time |
| The difference between different periods of switching (closing) |
| Closing (opening) Bouncing time (number of bounces) |
| Internal trigger test range: 1ms ~ 10000ms, resolution: 0.01ms, |
| External trigger test range: 1ms ~ 10000ms, |
| Resolution within 999ms: 0.01ms,1000-9999ms: 0.1ms, and over 10000ms: 1ms |
| Accuracy within 200ms: 0.05%± 0.1ms |
| velocity measurement |
instant separating (instant closing) velocity |
| Appointed time slot (stroke segment or angle segment) average |
| velocity |
| velocity measurement range |
0.1mm sensor 0.01~20.00m/s, |
| 345°angle sensor 1 cycle/ 0.01° |
| Travel measurement |
Travel of moving contact (travel) |
| Contact stroke (open distance) |
| Over travel |
| Overshoot or rebound stroke |
| Measuring range: |
linear sensor:50mm, measuring range: 0-50mm, resolution :0.1mm. |
| Optional 100-1000mm linear sensor of any length. |
| Encoder: 345° Rotate sensor, measurement |
| range: 0-1000mm, resolution :0.1°. |
| Current resistance range |
the maximum current 20 A, resolution: 0.01 A, 1000 Ω resistance, resolution: 0.01 Ω. |
| Instrument power supply |
AC 220V ± 10%; 50 hz plus or minus 10% |
| Dc power output |
continuously adjustable DC20 ~ 270V, DC220V≤20A (short time), Power: 4400W. |
| External trigger voltage |
AC/DC10-300V, current ≤120A |
| Disconnecting switch measurement range |
(1) Voltage output: DC20~270V(adjustable) |
| (2) Current output time: 0.01~10 s (settable) |
| (3) Fracture signal maximum acquisition time: 10s |
| (4) Measurable fracture closing, separation time, three-phase a synchronism, bounce time and frequency. |
| Mainframe volume |
360×260×170mm |
| Operating environmen |
-20℃~+50℃ |
| Relative humidity |
≤90% |