DC resistance of transformer is the, installation, handover test and preventive test by electric power department
Note: Regarding product purchase, technical maintenance and other services, welcome to send email: send email
Transformer DC Resistance Tester must be tested for their delivery, installation and handover, regardless they're semi-finished or finished transformers. It's also indispensable in preventive tests for power sector. In this way, manufacturing defects like coil material, welding, loose connection, lack of strands and disconnection can be detected and hidden dangers after it's put into use can be predicted. This DC resistance tester is developed by taking full use of our technical advantages in order to meet the needs of rapid measurement of transformer DC resistance. Integrating functions of three-phase tests (Yn, Y, △) and degaussing function, this new generation quick-testing device is ideal for measuring DC resistance of large transformers. Boasting a large true color high-resolution LCD screen, full-touch operation, it's simple and intuitive to use on site.It's fast to test with high accuracy and wide measurement range.
product names: Transformer dc resistance test in three channels、Dc resistance tachometer、Transformer dc resistance test instrument、 Transformer winding dc resistance test instrument、Transformer direct resistance speed meter、Transformer direct resistance quick test instrument、Inductive load Inductive load dc resistance rapid test instrument、Inductive load dc resistance test instrument,Transformer dc resistance test for three circuits、Three loop transformertest、Three channel dc resistance tester
| Output Current | Single Phase: 20A, 10A, 5A, 1A, 0.1A |
| Three Phase: 10A+10A, 5A+5A, 1A+1A, 0.1A+0.1A | |
| Measurement Range | Single Phase:
Gear 20A 0.5mΩ~1Ω
Gear 10A 1.0mΩ~2Ω
Gear 5A 10 mΩ~4Ω
Gear 1A 0.1Ω~20Ω Gear 0.1A 2.0Ω~200Ω |
| Three Phase:
Gear 10A+10A 0.5mΩ~0.8Ω
Gear 5A+5A 10mΩ~1.6Ω
Gear 1A+1A 0.1Ω~8.0Ω Gear 0.1A+0.1A 2.0Ω~80Ω |
|
| Accuracy | ±(Accuracy×0.2%+2) |
| Power Supply | AC220V±10%,50/60Hz |
| Temperature | -10°C~50°C |
| Relative Humidity | <90%, non-condensing |
| Dimension | 400mm×315mm×223mm |
| Weight | 9kg |
1.The appearance of the product shall be subject to the actual product,Technical parameters with model if there are any changes,without notice.In case of misappropriation or copying, legal liability will be investigated.
2. For more information about Wuhan UHV, please enter product center . Service email:info@hvtest.cc
1. Yn-type, Y-type and △-type winding can be tested in the same way as three phases, and their unbalance rate can be calculated.
2. Numerous on-site and off-site test demands of almost all transformers can be met with power supply of maximum output current being 20A, measurement range 0-200Ω, and the integration of degaussing function.
3. It can assist people to judge test data stability and prevent data misreading as resistance change rate within 5s, 15s and 30s can be automatically calculated during tests.
4. Numerous protections against back electromotive force, disconnection and power failure.
5. Equipped with a thermal printer, supporting 200 items of data storage locally and mass data storage in USB disks.
6. Comfortable and convenient user experience with fresh and simple 7-inch industrial true color screen, supporting operation by full touch control.
Transformer DC resistance tester measures the electrical resistance of transformer windings by applying a controlled direct current and measuring the corresponding voltage drop. Based on the measured electrical values, the instrument calculates the winding resistance and displays the result for analysis.
Winding resistance measurement is an important part of transformer manufacturing inspection, installation, commissioning, maintenance, and preventive testing. It can help identify potential problems such as loose connections, poor welding, broken conductor strands, and abnormal resistance differences between phases or winding sections.
The UHV-S10A DC Resistance Tester supports multiple output current settings and both single-phase and three-phase testing configurations. Selecting a suitable current range helps the operator obtain a stable reading within the instrument's specified measurement range.
For reliable results, the test connections should be secure, the transformer should be isolated according to the applicable safety procedure, and the measurement should be evaluated with consideration of winding temperature, tap position, and previous test records.
During DC resistance testing, direct current passes through the transformer winding and can leave residual magnetism in the transformer core. Depending on the transformer design and test conditions, this residual magnetism may influence subsequent tests and can contribute to increased magnetizing inrush current when the transformer is energized.
Transformer DC resistance tester with an integrated demagnetization function helps simplify the testing workflow by combining winding resistance measurement and demagnetization in one instrument. This can reduce the need to use a separate demagnetization device when the integrated function is suitable for the transformer and the required procedure.
The UHV-S10A combines DC resistance measurement with a built-in demagnetization function, making it useful for transformer commissioning, maintenance, and other testing tasks where winding resistance and residual magnetism need to be considered.
The appropriate demagnetization procedure depends on the transformer type, winding configuration, instrument settings, and applicable operating instructions. Users should follow the manufacturer's manual and the relevant safety procedures before returning the transformer to service.
1. Power Utilities and Substations: Used for delivery, installation, handover, and preventive testing of power transformers to detect manufacturing defects such as coil material issues, welding problems, loose connections, and broken strands.
2. Transformer Manufacturing: Employed by manufacturers for factory acceptance testing and quality control to verify winding resistance and ensure product quality before shipment.
3. Industrial and Mining Enterprises: Used for maintenance and testing of transformers in industrial facilities with high-voltage power systems.
4. Testing Laboratories: Suitable for use in high-voltage testing laboratories for conducting DC resistance tests on various transformer types.
5. Maintenance and Repair Facilities: Used during transformer maintenance and repair to verify the integrity of windings and connections after service work.
1. For testing winding of no-load regulating transformers, don't switch off no-load tap changer during tests or power discharging.
2. Don't disconnect test wires and cut off power switch during tests or power discharging.
3. During transformer tests, winding of the non-test side must be in open circuit.
1. Warranty card is included in the delivery of this product, so during delivery, please check the product carefully on the spot. If defects are found, please fill in the warranty card carefully.
2. Buyers enjoy lifelong maintenance from the date of purchase. They can show its warranty card for free repairing if problems happen within warranty period, otherwise, they have to pay for repairing and commissioning.
3. The following conditions are not in warranty:
Products are disassembled or their structure is changed by users deliberately.
Products are seriously damaged due to users' improper storage or use.
Products are damaged for other reasons on user side.
Enterprise products in strict accordance with international and national standards and rules of industry production, through the national, provincial and municipal electric power research institute and electric power authorities detection, measuring center, fully passed the ISO9001 international quality management system certification, the licence for manufacturing measuring instruments of the People's Republic of China, GB/T19001-2016 quality management system requirements, GB/T24001-2016 environmental management system requirements, GB/T45001-2020 occupational health and safety management system requirements.