| Charging voltage |
Setting range |
0~800kV |
| Scope of work |
10.0~800.0kV |
| Setting deviation |
≤±1% |
| Instability degree |
≤±1% |
| Setting resolution |
0.1kV |
| Charging time |
Setting range |
30~180s |
| Setting resolution |
1s |
| Alarm delay |
2s |
| Number of pressure |
Setting range |
1~999 |
| Protection setting |
Overcurrent protection value |
configurable |
| Overvoltage protection value |
configurable |
| Dynamic charge protection |
Can be Selected |
| Output impact stability |
Greater than 99% |
| Number of voltage boosting |
setting range |
1~999 |
|
100kV/5kJ
|
|
|
|
200kV5kJ
|
No truncation device, oscilloscope or acquisition card
|
6-10KV level switches and insulators; Lightning impulse voltage full wave test, waveform 1.2/50us
|
|
200kV10kJ
|
No truncation device, oscilloscope or acquisition card
|
6-10KV level switches and insulators; And the full wave test of lightning impulse voltage for transformers and mutual inductors without cutoff test requirements, waveform 1.2/50us
|
|
200kV10kJ
|
There is a truncation device, Tektronix 1102 oscilloscope or acquisition card
|
6-10KV level switches and insulators; And full wave lightning impulse voltage test for transformers and mutual inductors with waveform requirements of 1.2/50us; Cut wave 2-6us
|
|
300kV7.5kJ
|
No truncation device, oscilloscope or acquisition card
|
10-35KV level switches and insulators; Lightning impulse voltage full wave test, waveform 1.2/50us
|
|
300kV15kJ
|
No truncation device, Tektronix 1102 oscilloscope or acquisition card
|
10-35KV level switches and insulators; And full wave lightning impulse voltage test for transformers and mutual inductors without waveform cutoff test requirements, waveform 1.2/50us
|
|
300kV15kJ
|
300kV single-stage cutoff device, oscilloscope or acquisition card
|
10-35KV level switches and insulators; And full wave lightning impulse voltage test for transformers and mutual inductors with waveform requirements of 1.2/50us; Cut wave 2-6us
|
|
300kV30kJ
|
300kV single-stage cutoff device, Tektronix 2012 oscilloscope or acquisition card
|
10-35KV level switches and insulators; And full wave lightning impulse voltage test for transformers and mutual inductors with waveform requirements of 1.2/50us; Cut wave 2-6us
|
|
400kV10kJ
|
No truncation device, oscilloscope
|
10-35KV level switches and insulators; Lightning impulse voltage full wave test, waveform 1.2/50us
|
|
400kV20kJ
|
400kV single-stage cutoff device, oscilloscope
|
10-35KV level switches and insulators; And full wave lightning impulse voltage test for transformers and mutual inductors with waveform requirements of 1.2/50us; Cut wave 2-6us
|
|
400kV20kJ
|
No truncation device, oscilloscope or acquisition card
|
10-35KV level switches and insulators; And the full wave test of lightning impulse voltage for transformers and mutual inductors without cutoff test requirements, with a waveform of 1.2/50us;
|
|
400kV30kJ
|
300kV single-stage cutoff device, oscilloscope
|
10-35KV level switches and insulators; And full wave lightning impulse voltage test for transformers and mutual inductors with waveform requirements of 1.2/50us; Cut wave 2-6us
|
|
400kV40kJ
|
No truncation device, oscilloscope or acquisition card
|
10-35KV level switches and insulators; And full wave lightning impulse voltage test for transformers and mutual inductors with waveform requirements of 1.2/50us; Cut wave 2-6us
|
|
600kV15kJ
|
600kV single-stage steepening device, acquisition card
|
10-35KV level switch; And the insulator lightning impulse voltage full wave test with steep wave test requirements, waveform 1.2/50us; Steep wave
|
|
600kV30kJ
|
400kV single-stage cutoff device, oscilloscope
|
10-66KV level switches and insulators; And full wave lightning impulse voltage test for transformers and mutual inductors with waveform requirements of 1.2/50us; Cut wave 2-6us
|
|
500kV30kJ
|
Single stage truncation device, oscilloscope
|
|
|
800kV20kJ
|
|
10-110KV level switches and insulators; And full wave lightning impulse voltage test for transformers and mutual inductors without waveform cutoff test requirements, waveform 1.2/50us
|
|
800kV40kJ
|
No truncation device, oscilloscope
|
10-110KV level switches and insulators; And full wave lightning impulse voltage test for transformers and mutual inductors without waveform cutoff test requirements, waveform 1.2/50us
|
|
800kV40kJ
|
800kV cutoff device, oscilloscope
|
10-110KV level switches and insulators; And full wave lightning impulse voltage test for transformers and mutual inductors with waveform requirements of 1.2/50us; Cut wave 2-6us
|
|
800kV80kJ
|
800kV cutoff device, oscilloscope
|
10-110KV level switches and insulators; And full wave lightning impulse voltage test for transformers and mutual inductors with waveform requirements of 1.2/50us; Cut wave 2-6us
|