Suitable for large capacity, high voltage capacitive test and preventive test
Reference standard: GB 50150-2016, DL/T 849.6-2016, DL/T 474.4-2018
Note: Regarding product purchase, technical maintenance and other services, welcome to send email: send email
1, AC withstand voltage test for 10kV/300mm² cable 4.5km, capacitance ≤1.6897μF, test frequency 30-300Hz, test voltage 22kV, test duration 5 minutes.
2, AC withstand voltage test for 35kV/300mm² cable 2km, capacitance ≤0.389μF, test frequency 30-300Hz, test voltage 52kV, test duration 60 minutes.
3, AC withstand voltage test for 110kV/300mm² cable 0.5km, capacitance ≤0.0735μF, test frequency 30-300Hz, test voltage 128kV, test duration 60 minutes.
4, Full insulation AC withstand voltage test for 110kV/120MVA main transformer, capacitance ≤0.02μF, test frequency 45-65Hz, test voltage not exceeding 160kV, test duration 1 minute.
5, AC withstand voltage test for 110kV voltage level switch and other electrical equipment, test frequency 30-300Hz, test voltage not exceeding 265kV, test duration 1 minute.
| Serial number | Device name | Specification and model | Unit | Quantity |
| 1 | Variable frequency power supply | UHV-18kW | Tower | 1 |
| 2 | Excitation transformer | UHV-18kVA/4/8/16kV/0.4kV | Tower | 1 |
| 3 | High voltage reactor | UHV-67.5kVA/45kV | Section | 6 |
| 4 | Capacitive voltage divider | UHV-500pF/270kV | Set | 1 |
| Rated capacity | 405kVA |
| Rated voltage | 45kV;90kV;135kV;270kV |
| Rated current | 9A;4.5A;3A;1.5A |
| Measurement accuracy | System RMS level 1.5 |
| Operating frequency | 30-300Hz |
| Device output waveform | Sinusoidal wave |
| Quality factor | Device Q≥30(f=45Hz) |
| Waveform distortion rate | Output voltage waveform distortion ≤1% |
| Input power supply | Single-phase 220 or three-phase 380V voltage, frequency 50Hz |
| Working hours | Allow continuous 60min under rated load; Overpressure 1.1 times 1 minute |
| Temperature rise | Temperature rise ≤65K after continuous operation under rated load for 60 minutes |
| Protection function | Overvoltage, overcurrent, zero start, system mismatch (flashover) and other protection functions |
| Ambient temperature | -20℃-55℃ |
| Relative humidity | ≤90%RH |
| Altitude | ≤3000m |
| Serial number | Test | Test Frequency | Test Current |
| 1 | AC withstand voltage test for 10kV/300mm² cable 4.5km, capacitance ≤1.6897µF, test frequency 30-300Hz, test voltage 22kV, test duration 5 minutes. Use six reactors in parallel, L=90/6=15H | f=1/2π√(LC)=1/(2×3.14×√(15×1.6897×10⁻⁶))=31.61Hz | I=2πfCU=2π×31.61×1.6897×10⁻⁶×22×10³=7.38A |
| 2 | AC withstand voltage test for 35kV/300mm² cable 2km, capacitance ≤0.389µF, test frequency 30-300Hz, test voltage 52kV, test duration 60 minutes. Use two reactors in series (mutual inductance coefficient 1.15) and three groups in parallel, L=90×2×1.15/3=69H | f=1/2π√(LC)=1/(2×3.14×√(69×0.389×10⁻⁶))=30.72Hz | I=2πfCU=2π×30.72×0.389×10⁻⁶×52×10³=3.9A |
| 3 | AC withstand voltage test for 110kV/300mm² cable 0.5km, capacitance ≤0.0735µF, test frequency 30-300Hz, test voltage 128kV, test duration 60 minutes. Use three reactors in series (mutual inductance coefficient 1.15) and two groups in parallel, L=90×3×1.2/2=162H | f=1/2π√(LC)=1/(2×3.14×√(162×0.0735×10⁻⁶))=46.12Hz | I=2πfCU=2π×46.12×0.0735×10⁻⁶×128×10³=2.79A |
| 4 | Full insulation AC withstand voltage test for 110kV/120MVA main transformer, capacitance ≤0.02µF, test frequency 45-65Hz, test voltage not exceeding 160kV, test duration 1 minute. Use four reactors in series (mutual inductance coefficient 1.25), L=90×4×1.25=450H | f=1/2π√(LC)=1/(2×3.14×√(450×0.02×10⁻⁶))=53.05Hz | I=2πfCU=2π×53.05×0.02×10⁻⁶×160×10³=1.07A |
|
Test Object
Combination Method
|
Reactor Selection (67.5kVA/45kV Six Sections) |
Excitation Transformer Output Selection |
Test Voltage (kV) |
| 10kV/300mm 2 Cable 4.5km | Use six reactors in parallel (three of which are grounded) | 4kV | ≤22kV |
| 35kV/300mm 2 Cable 2km | Use two reactors in series and three groups in parallel | 4kV | ≤52kV |
| 110kV/300mm 2 Cable 0.5km | Use three reactors in series and two groups in parallel | 4kV | ≤128kV |
| 110kV/120MVA main transformer full insulation | Use four reactors in series | 8kV | ≤160kV |
| 110kV voltage level switch and other electrical equipment | Use six reactors in series | 16kV | ≤265kV |
| Rated Output Capacity | 18kW |
| Power Supply | 220/380±10%V (Single/Three Phase), Power Frequency |
| Output Voltage | 0-400V |
| Rated Input Current | 45A |
| Rated Output Current | 45A |
| Voltage Resolution | 0.01kV |
| Voltage Measurement Accuracy | 1.5% |
| Frequency Adjustment Range | 30-300Hz |
| Frequency Adjustment Resolution | ≤0.1Hz |
| Frequency Stability | 0.1% |
| Operating Time | Continuous 60min at Rated Capacity |
| Maximum Component Temperature at Continuous 60min Operation at Rated Capacity | ≤65K |
| Noise Level | ≤50dB |
| Dimensions (L×W×H mm) | 540×380×420 |
| Weight | Approximately 25kg |
| Rated Capacity | 18kVA |
| Input Voltage | 0-400V |
| Output Voltage | 4/8/16kV |
| Structure | Dry Type |
| Dimensions (L×W×H mm) | 520×520×460 |
| Weight | Approximately 150kg |
| Rated Capacity | 67.5kVA |
| Rated Voltage | 45kV |
| Rated Current | 1.5A |
| Inductance | 90H/unit |
| Quality Factor | Q≥30(f=45Hz) |
| Structure | Dry Type |
| Dimensions (Inner Diameter×Height mm) | 342×435 |
| Weight | Approximately 85kg |
| Rated Voltage | 270kV |
| High Voltage Capacitance | 500pF |
| Dielectric Loss | tgσ≤0.5% |
| Voltage Division Ratio | 3000:1 |
| Measurement Accuracy | Effective Value 1.5 Grade |
| Dimensions (Inner Diameter×Height mm) | 140×1000 |
| Weight | Approximately 8kg |
| No. | Equipment Name | Model and Specifications | Unit | Quantity |
| 1 | Variable Frequency Power Supply | UHV-18kW | Unit | 1 |
| 2 | Excitation Transformer | UHV-18kVA/4/8/16kV/0.4kV | Unit | 1 |
| 3 | High Voltage Reactor | UHV-67.5kVA/45kV | Section | 3 |
| 4 | Capacitive Voltage Divider | UHV500pF/270kV | Set | 1 |
| 5 | Internal Connection Cables | Set | 1 | |
| 6 | Factory Inspection Report | Copy | 1 | |
| 7 | User Manual | Copy | 1 | |
| 8 | Product Certificate | Copy | 1 | |
| 9 | Packing List | Copy | 1 |
| DL/T 596-1996 | "Preventive Test Code for Electric Power Equipment" |
| GB50150-2016 | "Standard for Handover Testing of Electrical Equipment in Electrical Installation Engineering" |
| GB10229-88 | "Reactors" |
| GB1094 | "Power Transformers" |
| GB1094.1-GB1094.6-96 | "Degrees of Protection Provided by Enclosures" |
| GB2900 | "Electrotechnical Terminology" |
| GB/T16927.1~2-1997 | "High Voltage Test Techniques" |
| DL/T474.4-2006 | "Guide for Insulation Test Implementation on Site - AC Withstand Voltage Test" |
| DL/T1015 | "Guide for the Use of Voltage Measurement Systems for On-site DC and AC Withstand Voltage Tests" |
| GB/T311.1-1997 | "Insulation Coordination and Insulation of High Voltage Power Transmission and Transformation Equipment" |
| GB191-2000 | "Pictorial Markings for Packaging and Storage" |
| JB/T9641-1999 | "Test Transformers" |
| IEC358(1990) | "Coupling Capacitors and Capacitor Dividers" |
| GB4793-1984 | "Safety Requirements for Electronic Measuring Instruments" |
| GB/T3859.2-1993 | "Application Guide for Semiconductor Converters" |
| GB/T2423.8-1995 | "Basic Environmental Testing Procedures for Electrical and Electronic Products" |
| DL/T849.6-2004 | "General Technical Specifications for Special Test Instruments for Power Equipment Part 6: High Voltage Frequency Tuning Test Devices" |
| Product Model | Primary Application | Rating(Capacity/Voltage) | Key Features |
| UHV-75kVA/75kV AC Resonant Test System | Smaller capacity cables & switchgear | 75kVA/75kV | Entry-level system for shorter cables and lower voltage tests; cost-effective with a simpler configuration (3 reactors). |
| UHV-135kVA/108kV Resonant Test Set for Cable | Medium-voltage cables & substation equipment | 135kVA/108kV | Optimized for 10kV and 35kV cables; flexible configuration (4 reactors); lightweight and portable for field testing. |
| UHV-270kVA/108kV High Voltage Resonant Test System | Longer or higher voltage cables | 270kVA/108kV | Higher capacity for testing longer cable runs or cables with higher voltage ratings; overlaps with the 135kVA system's application but offers greater capability. |
| UHV-405kVA/270kV Cable Resonant Test Set | High/Ultra-high voltage cables | 405kVA/270kV | Specifically designed for high-voltage cables (e.g., 110kV, 220kV) with significantly increased voltage and capacity. |
| UHV-540kVA/270kV High Voltage Test Set for 500kV GIS | 500kV GIS & other large capacitive loads | 540kVA/270kV | Highest capacity and voltage rating; designed for 500kV GIS substations and other EHV equipment, typically used for commissioning tests. |
1.The appearance of the product shall be subject to the actual product,Technical parameters with model if there are any changes,without notice.In case of misappropriation or copying, legal liability will be investigated.
2. For more information about Wuhan UHV, please enter product center . Service email:info@hvtest.cc
The UHV-405kVA/270kV series resonance scheme adjusts the power supply frequency to achieve resonance between the reactor and the test capacitor, thereby obtaining high voltage and large current on the test object. Due to its low required power supply, lightweight, and compact size, it has received widespread acclaim and application both domestically and internationally, representing a new method and trend in high-voltage testing.
The main functions and technical features of our company's frequency conversion resonance device are:
1, The device has protection functions such as overvoltage, overcurrent, zero-start, and system detuning (flashover). The overvoltage and overcurrent protection values can be set according to user needs. In case of a flashover, the flashover protection will activate and record the flashover voltage value for test analysis.
2, The entire device is lightweight, making it convenient for on-site use.
3, The device offers three working modes: fully automatic mode, manual mode, and automatic tuning with manual voltage boosting mode, allowing users to flexibly choose based on on-site conditions to improve testing speed.
4, It can store and remotely print data. The stored data is numbered digitally, making it easy for users to identify and search.
5, During automatic frequency scanning, the starting frequency can be set arbitrarily within a specified range, and the scanning direction can be chosen to be upward or downward. The large LCD screen displays the scanning curve, allowing users to intuitively understand whether the resonance point has been found.
6, Utilizing DSP platform technology, functions can be added or reduced, and upgrades can be made according to user needs, with a more user-friendly human-machine interface.
7, The required power supply capacity is significantly reduced. The series resonance power supply generates high voltage and large current through resonance between the reactor and the test object's capacitance. In the entire system, the power supply only needs to provide the active power consumed by the system, so the required power supply capacity is only 1/Q of the test capacity.
8, The weight and volume of the equipment are greatly reduced. In the series resonance device, the bulky high-power voltage regulator and conventional high-power frequency test transformer are eliminated. Moreover, the resonant excitation power supply only requires 1/Q of the test capacity, significantly reducing the system's weight and volume, typically to 1/10-1/30 of conventional test devices.
9, It effectively improves the output voltage waveform. The resonance power supply is a resonant filter circuit that can improve waveform distortion and obtain a good sine wave, effectively preventing harmonic peaks from causing mis-breakdown of the test object.
10, It prevents large short-circuit currents from burning the fault point. In a series resonance state, when the insulation weak point of the test object breaks down, the circuit immediately detunes, and the current rapidly drops to 1/Q of the normal test current. In contrast, when using parallel resonance or a test transformer for withstand voltage testing, the breakdown current immediately increases dozens of times. Compared to the two, the short-circuit current and breakdown current differ by hundreds of times. Series resonance can effectively find insulation weak points without the risk of large short-circuit currents burning the fault point.
11, No recovery overvoltage will occur. When the test object breaks down, the high voltage immediately disappears due to the loss of resonance conditions, and the arc extinguishes instantly. The process of re-establishing the recovery voltage is long, making it easy to disconnect the power supply before reaching the flashover voltage again. This voltage recovery process is an intermittent oscillation process of energy accumulation, which is long and will not result in any recovery overvoltage.
1. Extended Testing Capability: It can test 110kV/300mm² cables up to 0.5km (128kV test voltage) and perform full insulation tests on 110kV/120MVA main transformers (up to 160kV test voltage). This makes it suitable for high-voltage transmission class equipment.
2. Significant Weight and Size Reduction: Compared to traditional test transformers, the resonant design reduces the system's weight and volume to 1/10–1/30 of conventional equipment, greatly improving portability.
3. Low Power Supply Requirement: The power supply only needs to provide the active power losses (approximately 1/Q of the test capacity), allowing it to operate from a standard single-phase 220V or three-phase 380V supply.
4. Superior Safety: The resonant design inherently limits fault current to less than 1/Q of the normal test current during breakdown, preventing damage to the fault point and eliminating dangerous recovery overvoltages.
5. Excellent Waveform Quality: The low-distortion sinusoidal output (THD ≤1%) ensures reliable test results and protects the test object from harmonic-induced stress.
6. Proven Performance: The system's capability is verified with clear examples, such as testing 4.5km of 10kV/300mm² cable at 22kV for 5 minutes, or 2km of 35kV/300mm² cable at 52kV for 60 minutes.
1. AC Withstand Testing of High-Voltage Power Cables: It is particularly suited for testing 110kV XLPE cables, as well as longer runs of 10kV and 35kV cables.
2. AC Withstand Testing of Power Transformers: It can perform full insulation withstand tests on 110kV/120MVA class main transformers.
3. AC Withstand Testing of Switchgear: The system is applicable for testing 110kV voltage level switchgear and other electrical equipment, with test voltages up to 265kV.
4. Preventive and Handover Testing: It is designed for both periodic preventive maintenance tests and acceptance tests (handover tests) of high-voltage electrical equipment, complying with relevant standards like GB 50150-2016.
Enterprise products in strict accordance with international and national standards and rules of industry production, through the national, provincial and municipal electric power research institute and electric power authorities detection, measuring center, fully passed the ISO9001 international quality management system certification, the licence for manufacturing measuring instruments of the People's Republic of China, GB/T19001-2016 quality management system requirements, GB/T24001-2016 environmental management system requirements, GB/T45001-2020 occupational health and safety management system requirements.
email: info@hvtest.cc
Skype: Tina Qiao
+8615172408058
