Introduction


Transformer, GIS, SF6 switch, CT/PT, insulator, bus bar, cable, bushing, and others capacitive devices are the common primary electric equipment. Composed by power control cabinet, excitation transformer, reactor, voltage divider, connects silicon rectifier stack and micro ammeter with the voltage divider, then can finish the DC voltage withstand test.

Features


1.It with smaller volume, lighter weight compared with others reactors which in same voltage class and capacity. With small temperature rise under rated load; strong mechanical strength, good insulation performance, reliable.
2.The capacity of the power control cabinet is high; strong protection function; good output waveform; good stability; multi-function, easy to operate; single phase 220V or three phase 380V are available. 
3.Can match different kinds reactors, multifunctional, highly cost effective.

Parameters



Rated output voltage

0~1000kV 

Output frequency

30~300Hz

Voltage waveform

Sine wave,distoration≤1.0%

Working form

Full power continuous working time 60min

Quality factor

30~90

Frequency adjustment sensitivity 

0.1Hz

Instability

<0.05%

Power supply

Single phase 220V or three phase380V±10%

Frequency: 50Hz±5%

Serial product and application: 

Model

Application(10kV~500kV transformer substation AC voltage withstand equipment, frequency: 30~300Hz )

Frequency power source

Resonant reactor

Excitation transformer

Divider

Application

BPXZ-50/50/25

3kW

25kV/1A:2 sets
( dry type )

3kVA
( dry type )

50kV

10kV transformer ≤1000kVA
 10kVswitch, bus bar, PT,CT, etc.
 10kV(300mm2)cable≤1.0km

BPXZ-108/108/27

5kW

27kV/1A:4 sets
( dry type )

5kVA
( dry type )

110kV

 35kV transformer ≤31500kVA

 35kV switch, bus bar, PT,CT, etc.
 10kV(300mm2)cable: 2km
 35kV (300mm2)cable: 0.5km

BPXZ-200/200/50

10kW

50kV/1A:4 sets
( dry type )

10kVA
( dry type )

200kV

110kVtransformer≤ 50000kVA
 110kVGIS,PT,CT, etc.(preventive trial)
 35kV(300mm2)cable≤1.0km
 10kV (300mm2)cable≤2.0km

BPXZ-270/270/45

15kW

45kV/1A:6 sets
( dry type )

15kVA
( dry type )

300kV

110kVtransformer≤ 50000kVA
 110kVGIS,PT,CT, etc.
 35kV(300mm2)cable≤1.2km
 10kV (300mm2)cable≤3.0km

BPXZ-800/400/50

30kW

50kV/2A:8 sets
( dry type )
100kV/2A:4 sets
(oil immersed)

30kVA
( dry type )
30kA

(oil immersed)

400kV

 220kV transformer ≤80000kVA

 110kVtransformer≤ 50000kVA
 110kV/220kVGIS,PT,CT, etc.
 35kV(300mm2)cable≤2.0km
 110kV (300mm2)cable≤0.7km

BPXZ-1600/800/200

60kW

200kV/2A:4 sets
(oil immersed)

60kVA
( dry type )

800kV

 220kV transformer ≤80000kVA

 110kVtransformer≤ 50000kVA
 500kVGIS,PT,CT, etc.
 220kVswitch,GIS,PT,CT, etc.
 110kV(400mm2) cable≤1.5km
 220kV (400mm2) cable≤1.0km


Note: can make the solution according the parameters of the measured equipment
.


Accessory



Related Products


  • Brief Introduction for BPXZ Series Resonant System
  • BPXZ-HT Cable Resonance Test System
  • YDQ Power Frequency Withstand Voltage Test Set (Gas type)
  • SBF Triple Frequency Induced Withstand Voltage Test Set
  • HTDP-H VLF Hipot Test Set

Huatian All Rights Reserved Copyright © 2015-ICP:NO.10001395

Address: T4, No. 1, High-tech 2 Road,East Lake High-tech Development Zone, Wuhan